Introduction
Highly efficient, easy-to-deploy 100kW, 400V 3-phase UPS. Brings best-in-class power protection and low total cost of ownership to edge, small, and medium data centers, as well as critical infrastructure in commercial and industrial applications. Includes 5x8 start-up service and halogen-free cables. Marine certified.
Specifications
Main
- Main Input Voltage : 400 V 3 phases
- Other Input Voltage :
- Main Output Voltage :400 V 3 phases
- rated power in W : 100 kW
- rated power in VA : 100 kVA
- battery type
- External battery system : Li-Ion (Lithium-Ion)
VRLA
- provided equipment :
- Dust filter
- EcoStruxure IT ready (UPS)
- Installation guide
- Integrated network management
- Power modules ship installed
- Start-up service
General
- bypass voltage tolerance : +/- 10 %
- redundant : No
Physical
- colour : White
- height : 148.5 cm
- width : 52.1 mm
- depth : 84.7 cm
- net weight : 250 kg
- USB compatible : No
Input
- network frequency : 40...70 Hz
- input voltage limits : 340...460 V 400 V
- maximum input current : 180 A
- max short time withstand current : 65 kA
- input harmonic distortion : Less than 3 % for full load
- load power factor : From 0.7 leading to 0.7 lagging without any derating
Output
- Maximum configurable power in W : 50 kW
- output frequency
- 50 Hz sync to mains
- 60 Hz sync to mains
- 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
- 60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised
- crest factor :2.5
- Wave type : Sine wave
- output voltage tolerance :+/-1% after 50ms
- output harmonic distortion : < 1% linear load and < 5% non-linear load
- output overload operation : 10 minutes at 125% and 60 seconds at 150%
- bypass type : Built-in static bypass
- Maximum configurable power in VA : 100 kVA
Conformance
- standards
- EN/IEC 62040-1
- EN/IEC 62040-2
- FCC part 15 class A
- IEC 60721-4-2 level 2M2
- UL 1778 5th edition
Environmental
- ambient air temperature for operation : 0…40 °C
- relative humidity : 0…95 % non-condensing
- operating altitude : 0...3300 ft
- ambient air temperature for storage : -25…55 °C
- storage Relative Humidity : 10…80 % Non-condensing
- acoustic level : 68 dBA
- heat dissipation : 5804 Btu/h
- IP degree of protection : IP21
Batteries & Runtime
- battery voltage : 480...576 V DC
- discharge battery voltage : 384 V DC
- max current discharge : 271 A
- Battery power in VAH : 0 VAh runtime
- extended runtime :0
Communications & Management
- control panel: Touch screen LCD user interface
- alarm : Audible and visible alarms prioritized by severity